Power Factor: kW, kVA and Amps, Worked Step by Step

/ 6 min read / By CircuitDrill

Power factor questions look harder than they are. The exam gives you a load in kilowatts, a power factor, and a voltage, then asks for amps. This article walks through the idea, the formulas, and two worked examples, so you can do it the same way every time.

Three kinds of power

An AC load has three related power numbers. Real power, in kilowatts (kW), is the part that does work. Apparent power, in kilovolt-amperes (kVA), is volts times amps. Power factor is the ratio of the two: kW divided by kVA. It is a number from 0 to 1.

The physics comes from the phase angle between voltage and current. The OpenStax University Physics Volume 2, section 15.4 gives average AC power as P = Vrms x Irms x cos φ, and calls cos φ the power factor. For a resistor the angle φ is zero, so the power factor is 1. For an ideal capacitor or inductor the angle is 90 degrees, cos φ is 0, and the average power is 0, because the element stores energy in one half-cycle and returns it in the other.

Why the amps go up when power factor goes down

Current is tied to apparent power, not to real power. Apparent power is kW divided by power factor. So for the same kW, a lower power factor means more kVA, and more kVA at the same voltage means more amps. The conductors, the overcurrent device, and the transformer all feel that extra current, even though the work done is the same.

The formulas

Single-phase

  • kVA = kW / PF
  • Amps = kVA x 1000 / volts

Balanced three-phase

The Iowa State University course note EE 303, Three-Phase Circuits gives the balanced three-phase relations in line values: real power P = √3 x VL x IL x cos θ, and apparent power |S| = √3 x VL x IL. It also notes that these line-value formulas apply to both wye and delta connections. Solving for the line current gives:

  • kVA = kW / PF
  • I = kVA x 1000 / (1.732 x VL), where VL is the line-to-line voltage

The number 1.732 is the square root of 3, rounded. The same note gives the wye relation VL = √3 x Vphase, which is where that factor comes from.

Worked example 1: single-phase

A single-phase load uses 4.8 kW at a power factor of 0.80 on a 240 V supply.

  1. kVA = 4.8 / 0.80 = 6.0 kVA
  2. Amps = 6,000 / 240 = 25 A

If you forget the power factor and divide 4,800 W by 240 V, you get 20 A. That is 5 A too low, and it is the most common slip on this kind of question.

Worked example 2: three-phase

A balanced three-phase load uses 50 kW at a power factor of 0.80 on 480 V line-to-line.

  1. kVA = 50 / 0.80 = 62.5 kVA
  2. I = 62,500 / (1.732 x 480) = 62,500 / 831.4 = 75.2 A

Now compare the same 50 kW at a power factor of 1.00. The kVA is 50 and the current is 50,000 / 831.4 = 60.1 A. The lower power factor adds about 15 A, roughly 25 percent more current, for the same work.

Power factorkVA for 50 kWCurrent at 480 V, three-phase
1.0050.060.1 A
0.9055.666.8 A
0.8062.575.2 A

Practice question

A balanced three-phase load uses 30 kW at a power factor of 0.75 on 208 V line-to-line. What is the line current?

  1. kVA = 30 / 0.75 = 40 kVA
  2. I = 40,000 / (1.732 x 208) = 40,000 / 360.3 = 111.0 A

The wrong answers on a multiple-choice version are easy to predict. Skipping the power factor gives 30,000 / 360.3 = 83.3 A. Forgetting 1.732 gives 30,000 / 208 = 144.2 A. If your result matches one of those exactly, check which step you skipped.

A short checklist

  • Write down kW, power factor, and voltage before you touch the calculator.
  • Divide kW by the power factor to get kVA.
  • Use 1.732 for three-phase only, and use the line-to-line voltage.
  • Round at the end, not in the middle.
  • Check that the answer is larger than the no-power-factor answer. If it is not, a step is missing.

Common ways to lose points

Most wrong answers come from four habits. The first is dividing by voltage without first converting kW to kVA. The second is multiplying by the power factor instead of dividing by it, which makes the current smaller when it should be larger. The third is using 1.732 on a single-phase load. The fourth is using phase voltage in a formula that expects line-to-line voltage. Write the formula on your scratch paper before you plug in numbers, and the habit will protect you under time pressure.

What this does not cover

This article is about the arithmetic. It does not tell you how to size conductors or protection for a real installation. For that, follow the code edition adopted in your jurisdiction and ask your local authority having jurisdiction. Exams also differ on what they give you, so read each question for the power factor, the voltage type, and whether the load is single-phase or three-phase.

CircuitDrill is an independent study tool and is not affiliated with NFPA or any licensing board. If you want more questions like this, the free practice and the full course are on the CircuitDrill home page.

Frequently asked questions

How do I convert kW to kVA?

Divide kW by the power factor. For example, 50 kW at a power factor of 0.80 is 62.5 kVA.

Why does a lower power factor mean more amps?

Current follows apparent power (kVA). For the same kW, a lower power factor gives more kVA, so the current is higher at the same voltage.

When do I use 1.732 in a current calculation?

Use 1.732, the square root of 3, for balanced three-phase loads with line-to-line voltage. Do not use it for single-phase loads.

Does this tell me how to size conductors?

No. It covers only the arithmetic. Follow the code edition adopted in your area and your local authority having jurisdiction.