CircuitDrillCircuitDrill

Home / Blog / Conversions

Conversions

kW, Horsepower and BTU/h Conversions for the Electrician Exam

/ 6 min read / By CircuitDrill

Electrical exam problems mix kilowatts, horsepower and BTUs per hour, and the arithmetic is only ever a multiplication or a division by a fixed factor. The points are lost by picking the wrong direction or by mixing up a BTU with a BTU per hour. This guide gives the factors, where they come from, and worked problems for heaters, water heating and air conditioning.

The factors you need

ConversionFactorSource
Horsepower (electric)1 hp = 746 WNIST, exact
Horsepower (550 ft·lbf/s)1 hp = 745.7 WNIST
Kilowatt to BTU per hour1 kW = 3,412 BTU/hEIA and NIST
Ton of refrigeration1 ton = 12,000 BTU/h = 3.517 kWNIST
Gallon of water1 gal = 8.34 lbUSGS
Kilowatt-hour1 kWh = 3.6 million J = 3,412 BTUNIST and EIA

The NIST Guide to the SI, Appendix B.8 lists 746 W for the electric horsepower as an exact value, 745.7 W for the horsepower defined as 550 foot-pounds per second, and 0.2930711 W for one BTU per hour. Divide 1,000 W by 0.2930711 and you get 3,412 BTU/h for a kilowatt. The U.S. Energy Information Administration states the same figure as 1 kilowatt-hour = 3,412 BTU. Some sources round it to 3,413. The DOE's water heater selection guideline uses 3,413 in one footnote. If a problem hands you a factor, use that one.

The direction rule

  • kW to BTU/h: multiply by 3,412. The answer is a bigger number.
  • BTU/h to kW: divide by 3,412. The answer is a smaller number.
  • hp to watts: multiply by 746.
  • Watts to hp: divide by 746.

Sanity check: a BTU per hour number is always about 3,400 times its kilowatt number. If your answer is not near that ratio, you went the wrong way.

BTU versus BTU per hour

A BTU is an amount of energy. EIA defines one BTU as the heat needed to raise one pound of water by one degree Fahrenheit. A BTU per hour is a rate, the same kind of quantity as a watt. One kilowatt-hour of energy equals 3,412 BTU, and a power of one kilowatt equals 3,412 BTU per hour. Mixing the two is the most common unit error in this topic.

Problem 1: kilowatts to BTU per hour

A resistance heating element is rated 4.5 kW. The DOE guideline notes that a typical electric water heater has two 4.5 kW elements. What is the heat output in BTU per hour?

  • 4.5 × 3,412 = 15,354 BTU/h

Problem 2: BTU per hour to kilowatts and amps

A resistance heater is rated 20,000 BTU/h and runs on 240 V single-phase. Find the power in kilowatts and the current.

  • kW = 20,000 / 3,412 = 5.86 kW, or 5,862 W
  • I = P / E = 5,862 / 240 = 24.4 A

This works because a resistance heater turns essentially all of its electrical input into heat. Heat pumps and other equipment do not follow this shortcut, and exam problems will say so.

Problem 3: heating water

How long does a 4.5 kW element need to raise 50 gallons of water by 70°F? Ignore heat losses.

  • Weight of water = 50 × 8.34 = 417 lb
  • Heat needed = 417 × 70 = 29,190 BTU
  • Element output = 15,354 BTU/h
  • Time = 29,190 / 15,354 = 1.90 hours
  • Check in kWh: 29,190 / 3,412 = 8.55 kWh, and 8.55 / 4.5 = 1.90 hours

The USGS conversion table gives 8.34 pounds per gallon. Real tanks lose some heat while they heat, so a real heater takes a little longer than this ideal figure.

Problem 4: air conditioning tons

A 3-ton air conditioner has a cooling capacity of 3 × 12,000 = 36,000 BTU/h. In kilowatts that is 36,000 / 3,412 = 10.55 kW of heat removal, or 3 × 3.517 = 10.55 kW using the NIST ton factor. The ton here is a rate of heat removal. It is not the electrical power the unit draws, and it is not a weight. The electrical input depends on the equipment's efficiency, which an exam problem has to give you.

Problem 5: horsepower to watts

A 3 hp motor delivers 3 × 746 = 2,238 W at the shaft. That is output power. A motor draws more electrical power than it delivers, because some of its input becomes heat. OpenStax University Physics works one such case in Electrical Energy and Power: a DC winch motor consumes 2,300 W but delivers about 1,633 W of lifting power, and the difference is dissipated as heat. For current in an actual motor circuit, exam problems follow your adopted code edition's tables and not this conversion, as covered in the motor circuit guide.

Common mistakes

  • Going the wrong way. Multiply for kW to BTU/h, divide for BTU/h to kW.
  • Dropping the 1,000. 746 W is 0.746 kW. Keep units consistent.
  • Treating a BTU as a BTU per hour. One is energy, the other is a rate.
  • Treating hp as input power. Horsepower on a motor describes output.
  • Reading a ton as a weight. In cooling, a ton is 12,000 BTU/h.
  • Ignoring the factor in the problem. If it says 3,413, use 3,413.

Self-check

A 2 kW heater is about how many BTU per hour?

2 × 3,412 = 6,824 BTU/h.

A 9,000 BTU/h heater draws how many kilowatts?

9,000 / 3,412 = 2.64 kW.

How many watts does a 5 hp motor deliver at the shaft?

5 × 746 = 3,730 W.

Keep practicing

These are study conversions. Equipment ratings and installation rules come from the manufacturer, the National Electrical Code edition adopted in your state, and your authority having jurisdiction (AHJ). For timed practice on Ohm's law, power and conversion problems, see the Ohm's law guide and the CircuitDrill Calculations Course, which has 308 exercises and four timed practice exams for a one-time $59. See the course page. CircuitDrill is an independent study tool, not affiliated with NFPA, the National Electrical Code, or any state licensing board.

Frequently asked questions

How many BTU per hour is one kilowatt?

About 3,412 BTU per hour. NIST lists 1 BTU per hour as 0.2930711 W, and EIA gives 1 kWh = 3,412 BTU. Some sources round to 3,413.

How many watts is one horsepower?

NIST lists the electric horsepower as exactly 746 W. The horsepower defined as 550 foot-pounds per second is 745.7 W.

Is a BTU the same as a BTU per hour?

No. A BTU is an amount of heat energy. A BTU per hour is a rate, like a watt. One kilowatt-hour is 3,412 BTU and one kilowatt is 3,412 BTU per hour.

What does a ton mean on an air conditioner?

A ton of refrigeration is 12,000 BTU per hour of heat removal, about 3.517 kW. It describes cooling capacity, not weight and not electrical input.

FREE TOOL

Voltage drop calculator with every step shown

Single-phase or three-phase, copper or aluminum, 14 AWG to 500 kcmil.