Neutral Current on a 120/240 V Circuit: The Difference Rule
A 120/240 V single-phase service has two hot conductors and a neutral. Exam questions love to ask what the neutral carries, and the answers people give are usually one of two wrong ones: the full load, or nothing at all. The right answer sits in between. This guide shows the rule, why it works, and four situations you can check with a pencil.
How the 120/240 V system is built
A split-phase supply is two 120 V sources connected in series, with the neutral at the midpoint. Between either hot conductor and the neutral you have 120 V. Between the two hot conductors you have 240 V. Kuphaldt's open textbook describes this arrangement in Lessons in Electric Circuits, Volume II, Single-Phase Power Systems, and the Wikipedia article on split-phase power adds that the two 120 V lines are 180 degrees out of phase with each other.
That 180 degree relationship is the whole story. Current going out on one hot leg and current going out on the other hot leg flow in opposite directions at the neutral, so they cancel as far as they can.
The rule: the neutral carries the difference
- Balanced loads: when the two sides consume equal power, the neutral carries zero current.
- Unbalanced loads: the neutral carries only the difference between the two leg currents.
Both statements come straight from the textbook. In formula form, using I = P / V for each 120 V load (see OpenStax University Physics, Electrical Energy and Power):
- Leg current = total watts of 120 V loads on that leg / 120
- Neutral current = larger leg current minus smaller leg current
This is the textbook rule for the resistive loads used in exam problems. Read each question for any extra assumption it gives you about the loads.
Problem 1: two 120 V loads
Leg 1 feeds a 1,800 W load and leg 2 feeds a 1,200 W load, both at 120 V. What does the neutral carry?
- Leg 1 = 1,800 / 120 = 15 A
- Leg 2 = 1,200 / 120 = 10 A
- Neutral = 15 minus 10 = 5 A
Problem 2: add a 240 V load
Now add a 4,500 W, 240 V water heater. It connects between the two hot conductors, not to the neutral.
- Heater current = 4,500 / 240 = 18.75 A on each hot conductor
- Leg 1 = 15 + 18.75 = 33.75 A
- Leg 2 = 10 + 18.75 = 28.75 A
- Neutral = 33.75 minus 28.75 = 5 A
The neutral current did not change. A 240 V load raises the current on both hot conductors by the same amount, so it adds nothing to the difference. The heater adds the same 18.75 A to both hot conductors and nothing to the neutral.
Problem 3: only one leg is loaded
Suppose leg 1 carries 15 A and leg 2 carries nothing. The difference is 15 minus 0 = 15 A, so the neutral carries the whole 15 A. This is the ordinary 120 V circuit: the neutral returns what the hot conductor sends out.
Four situations side by side
| Situation | Leg 1 | Leg 2 | Neutral |
|---|---|---|---|
| Balanced 120 V loads | 15 A | 15 A | 0 A |
| Unbalanced 120 V loads | 15 A | 10 A | 5 A |
| One leg only | 15 A | 0 A | 15 A |
| 240 V load only (4,500 W) | 18.75 A | 18.75 A | 0 A |
What about three-phase?
A 120/208 V three-phase wye system has three hot conductors 120 degrees apart, with 208 V between any two. Kuphaldt's chapter on three-phase power systems says that with equal loads on all three phases the neutral wire carries no current at all, and that its purpose is to keep each load working if one of the others fails open. The unbalanced three-phase case needs a longer calculation and is not covered here.
Common mistakes
- Adding the two legs. 15 + 10 = 25 A is not the neutral current. The answer is 15 minus 10 = 5 A.
- Counting 240 V loads on the neutral. They connect hot to hot and never use it.
- Saying the neutral always carries the full load. That is true only when one leg is loaded and the other is empty.
- Saying the neutral never carries anything. It carries the imbalance, which is the imbalance between the legs.
- Using 240 V to find the current of a 120 V load. Use the voltage the load is connected across.
Self-check
Leg 1 carries 24 A and leg 2 carries 18 A of 120 V loads. What does the neutral carry?
6 A. The neutral carries the difference: 24 minus 18.
A 5,000 W, 240 V load is the only load on a panel. What does the neutral carry?
0 A. The load draws 20.83 A on each hot conductor and nothing on the neutral.
A 1,200 W, 120 V load is on leg 2 and nothing is on leg 1. What does the neutral carry?
10 A. With one leg empty, the neutral carries the whole current of the loaded leg.
Keep practicing
This guide explains the circuit theory behind neutral current questions. Rules for sizing the neutral and for how loads are counted come from the National Electrical Code edition adopted in your state and your authority having jurisdiction (AHJ), so check both. They are not covered here. For timed practice on Ohm's law and load problems, the CircuitDrill Calculations Course has 308 exercises and four timed practice exams for a one-time $59. See the course page. CircuitDrill is an independent study tool, not affiliated with NFPA, the National Electrical Code, or any state licensing board.
Frequently asked questions
What does the neutral carry on a 120/240 V circuit?
Only the difference between the two hot leg currents. With equal 120 V loads on both legs it carries zero. With one leg loaded and the other empty it carries the whole current of the loaded leg.
Do 240 V loads put current on the neutral?
No. A 240 V load connects between the two hot conductors, so it raises both leg currents equally and adds nothing to the difference.
How do I find the current on each leg?
Add the watts of the 120 V loads on that leg and divide by 120. Add any 240 V load current to both legs if you need the hot conductor current.
What about three-phase?
In a balanced 120/208 V three-phase wye system the neutral carries no current. Unbalanced three-phase neutral current needs a longer calculation.