Wire sizes
AWG and Circular Mils: The Rule of 3 and the Rule of 10
AWG numbers run backwards, and that trips people up on exam day. Underneath the odd numbering there is a clean pattern: every wire size is the same fixed step thicker than the one before it. Once you know the pattern you can estimate circular mils in your head, check a table lookup, and see at a glance how much a size change helps a voltage drop problem. This guide gives the three rules of thumb and shows where they come from.
What a circular mil is
A mil is one thousandth of an inch. A circular mil is a unit of area: the area of a circle one mil in diameter. That makes the area in circular mils simple to find. As the CED Engineering conductor course, adapted from a U.S. Navy training manual, puts it, you square the diameter in mils. Its example is a 25 mil wire: 25² = 625 circular mils.
A 12 AWG wire is 80.8 mils across, so its area is 80.8² = 6,529 circular mils. The table value is 6,530. One circular mil is π/4 of a square mil, or about 0.0005067 square millimeters, according to the Wikipedia article on the circular mil. That puts 6,530 CM at about 3.31 mm², the same area OpenStax computes for a 2.053 mm copper wire in its resistivity and resistance chapter. Large wires are measured in thousands of circular mils, written kcmil or MCM.
Where the pattern comes from
ASTM B258 defines the AWG sizes. According to the AWG article, 36 AWG is 0.005 inch across and each size up the scale multiplies the diameter by the 39th root of 92, which is about 1.1229. So each size is about 12 percent thicker than the next one down, and that fixed ratio gives three rules of thumb:
- Every 3 sizes: the area doubles. The area ratio per size is 1.1229² = 1.261, and 1.261³ = 2.005.
- Every 6 sizes: the diameter doubles (and the area is four times larger).
- Every 10 sizes: the area is about ten times larger. 1.261 to the 10th power = 10.2.
Remember the direction: a lower AWG number is a bigger wire. "Three sizes up" in this guide means three numbers lower.
Check the rules against a table
These values come from a published copper wire table, which rounds to three digits:
| AWG | Diameter (mils) | Circular mils |
|---|---|---|
| 14 | 64.1 | 4,110 |
| 12 | 80.8 | 6,530 |
| 10 | 102 | 10,380 |
| 8 | 128 | 16,500 |
| 6 | 162 | 26,300 |
| 4 | 204 | 41,700 |
| 2 | 257 | 66,400 |
Source: Ness Engineering, Bare Copper Wire Data. Every two rows the area grows by about 1.6, which is 1.261 squared. Different published tables differ in the last digit or two, so on the exam use the exact value in the table you are given.
Problem 1: rule of 3
6 AWG is 26,300 circular mils. Estimate 3 AWG.
- 3 AWG is three sizes bigger than 6 AWG, so the area doubles.
- 26,300 × 2 = 52,600 CM
- The table value for 3 AWG is 52,600 CM.
Problem 2: rule of 10
12 AWG is 6,530 circular mils. Estimate 2 AWG.
- 12 to 2 is ten sizes, so the area is about ten times larger.
- 6,530 × 10 = 65,300 CM
- The table value is 66,400 CM, so the estimate is within 2 percent.
Problem 3: rule of 6
10 AWG is 10,380 circular mils. Estimate 4 AWG.
- 10 to 4 is six sizes, so the diameter doubles and the area is four times larger.
- 10,380 × 4 = 41,520 CM
- The table value is 41,700 CM.
Problem 4: what a size change does to voltage drop
The voltage drop formula divides by circular mils, so the rule of 3 tells you how a size change plays out. In the worked example in the voltage drop guide, a 120 V, 20 A, 100 ft run on 12 AWG copper drops 6.58 percent. Resistance is inversely proportional to area, as OpenStax shows in R = ρL/A, so three sizes up (about double the area) should cut the drop to about half.
- Estimated drop = 6.58 / 2 = about 3.3 percent
- Check: 9 AWG is about 13,100 CM, and 2 × 12.9 × 20 × 100 / 13,100 = 3.94 V, which is 3.28 percent of 120 V
The estimate matches. Use it to sanity check a table lookup: if you jumped three sizes and the drop did not roughly halve, something is wrong.
Common mistakes
- Reading AWG backwards. A lower number is a bigger wire.
- Doubling the area every size. The area doubles every three sizes.
- Mixing up diameter and area. Six sizes doubles the diameter. The area is four times larger.
- Forgetting to square. Circular mils are the diameter in mils squared, not the diameter itself.
- Using the rules instead of the table. The rules estimate and check. The exam wants the table value.
Self-check
8 AWG is about 16,500 CM. About what is 5 AWG?
5 AWG is three sizes bigger, so about 33,000 CM. A table lists 33,100.
How many sizes make the diameter double?
Six sizes.
Which is the bigger wire, 14 AWG or 10 AWG?
10 AWG. A lower AWG number is a bigger wire.
Keep practicing
These rules are study shortcuts. Conductor sizes, areas and ampacities for real installations come from the tables in the National Electrical Code edition adopted in your state and from your authority having jurisdiction (AHJ). For timed practice on voltage drop and conductor problems, try the free voltage drop calculator, then the CircuitDrill Calculations Course, which has 308 exercises and four timed practice exams for a one-time $59. See the course page. CircuitDrill is an independent study tool, not affiliated with NFPA, the National Electrical Code, or any state licensing board.
Frequently asked questions
What is a circular mil?
A circular mil is the area of a circle one mil (0.001 inch) in diameter. The area of a round wire in circular mils is its diameter in mils squared.
How many AWG sizes double the area of a wire?
Three. Going down three AWG numbers doubles the cross-sectional area, and going down six doubles the diameter.
Is a higher AWG number a bigger or smaller wire?
Smaller. A lower AWG number is a bigger wire, so 10 AWG is larger than 14 AWG.
What is the difference between kcmil and MCM?
Nothing. Both mean thousands of circular mils and are used for wires larger than 4/0 AWG.